Picture of R55 Control Panels - 1 Conveyor - Selectable - 10 minutes

R55 Control Panels - 1 Conveyor - Selectable - 10 minutes


This control panel is for one conveyor; it is configurable in either semi-automatic mode or automatic mode if used in conjunction with an E1P-57107 final sensor with the integral timer; this provides automatic stop and auto re-start delays of up to 10 minutes.

If two conveyors are operating as twins; i.e. picking up from a single silo, and delivering material into one building, but are not connected in any other way then you would use two of these control panels; each conveyor operating independently.

 

The control units are housed in rugged IP65 enclosures; they provide a high level of environmental protection making them suitable for most environments; they house the motor starter and its thermal overload protection relay.

 

The E5R-1CS Control Panels has two modes; semi-automatic and fully automatic:

 

Semi automatic mode

 

The panel is delivered as standard in semi automatic mode; it is compatible with either the E1P-57107 proximity sensor with its time delay set to zero or a paddle switch E5P-S?BNT.

 

Operation – The conveyor requires a manual start initiating by the operator; the system is stopped automatically when material covers the final sensor; the conveyor will not re-start until the unit is re-started manually. The conveyor will not be able to start unless the final sensor is clear.

 

Automatic mode

 

The E1P-57107 final sensor with the integral timer must be used in this configuration and the timer adjusted to give a re-start signal at no less than a two minute interval; the maximum re-start delay is ten minutes. If a longer delay is required then the E5R-1CA panel should be specified in place of this panel.

 

Operation – When the control panel is powered up the delay set on the sensor will elapse and the conveyor will start; the system will stop automatically when material covers the final sensor. When material has cleared the sensor the time delay will start elapsing, when the time delay has elapsed the conveyor will re-start, and complete the cycle. (See notes on how to set the correct time delay)

 

General specification:

  • Suits 0.37Kw, 0.75Kw, 1.1Kw & 2.2Kw single or three phase motors.
  • 230v AC operating coil – Requires Neutral supply
  • A manual start button and latching stop button are situated on the front panel; the latching stop button can also be used to inhibit the automatic sequence if that mode is selected.
  • Enclosure IP65 rated c/w 20mm knockouts.
 